Commissioning
Connecting the device to a Siemens PLC in PROFINET
40
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
8.7.5 Configuring device functions
The FEN20-4IOL appears as a modular slave with eight empty virtual slots. Slots 0 and Basic are
pre-configured.
The function of these eight slots is either defined via GSDML or can only be used for a specific
purpose.
Slot Meaning
0 Main module turck-fen20-4iol (default name)
Parameterization of functions (protocol deactivation, etc.), which concern
the complete module.
0 X1 Parameterization of PROFINET functions (MRP, etc.)
0 X1 P1 Parameterization of the Ethernet port properties (topology, connection op-
tions etc.).
0 X1 P2
Basic Parameters/diagnostics of the IO-Link channels of the device, if the ports
are used as pure digital channels (DI/DXP)
IO-Link port 1…4 Configuration of the IO-Link ports
Diagnostics Optional mapping of the diagnostics (IO-Link and DXP diagnostics) into
the master's process image.
IO-Link Events Optional mapping of the IO-Link events into the master's process image.
VAUX Control Optional mapping of the VAUX diagnostics into the master's process im-
age.
Module status Optional mapping of the module status into the masters process image.
Configuring th IO-Link Ports (Example)
IO-Link-Port
(Hardware)
Process data
length
Sensor GSDML entry
Port 1 2 byte IN Turck temperature
sensor,
TS-530-LI2UPN8X-...
Port configuration generic:
IN 1 WORD
Port 2 1 Bit IN - DI
Port 3 2 byte IN Turck linearity sensor,
Li100P0-Q25LM0-...
Port configuration specific:
Li100P0-QU25L
Port 4 2 byte IN
2 byte OUT
Turck I/O hub,
TBIL-M1-16DXP
Port configuration specific:
TBIL-M1-16DXP