V01.00 | 2019/12
97
The default values are shown in bold type.
Parameter name Value Meaning Description
Dec. Hex.
Manual output re-
set after overcur-
rent (SROx)
0 0x00 Yes
The output switches on automatically after an over-
load.
1 0x01 No The output is manually switched-off after an overload
until a new set-command is given (rise and fall).
Activate output
Chx (DXPx_ENDO)
0 0x00 Yes
The output at pin 2 is deactivated.
1 0x01 No The output at pin 2 is activated.
Operation mode
0 0x00 IO-Link without valida-
tion
Pin 4 is operated in IO-Link mode.
The master does not check if the connected device
matches the configured one.
1 0x01 IO-Link with compatible
device
Pin 4 is operated in IO-Link mode.
The master checks if the Vendor ID and the MSB of
the Device ID (this byte defines the product family) of
the connected device match those of the configured
one. If the master detects a mismatch, the IO-Link
communication is established, but there is no process
data exchange. The device remains in the safe state
(Pre-Operate).
Parameters and diagnostic information can be read
and respectively written.
2 0x02 IO-Link with compatible
device
Pin 4 is operated in IO-Link mode.
The master checks if the Vendor ID and the Device ID
of the connected device match those of the con-
figured one. If the Vendor ID matches, but the Device
ID not, then the master tries to write the Device ID to
the device. If the writing is successful, then the device
is a compatible one, process data exchange is pos-
sible. If writing the Device ID is not successful, then
process data exchange is not possible. The device re-
mains in the safe state (Pre-Operate).
Parameters and diagnostic information can be read
and respectively written.
3 0x03 IO-Link with identical
device
Pin 4 is operated in IO-Link mode.
The master checks if the device type (Vendor ID and
Device ID) and the serial number of the connected
device match the data of the configured one. If the
master detects a mismatch, the IO-Link communica-
tion is established, but there is no process data ex-
change. The device remains in the safe state (Pre-Op-
erate).
Parameters and diagnostic information can be read
and respectively written.