Parameterizing and Configuring
Parameters
98
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Parameter name Value Meaning Description
Dec. Hex.
Operation mode 4 0x04 DI (with parameter access) Pin 4 is generally operated as simple digital input.
However, an acyclic parameter access from the PLC or
the DTM is possible. The IO-Link master starts the port
in IO-link mode, parameterizes the device and sets
the port back into SIO mode (SI). The port remains in
SIO mode (DI) until a new IO-Link request is sent from
the higher-level control.
Data storage is not supported. Connected devices
have to support the SIO mode (DI).
In case of a parameter access, the IO-Link communic-
ation at the port is started. Switching signals are inter-
rupted.
8 0x08 DI Pin 4 is operated as simple digital input. Data storage
is not supported.
9 0x09 DX The channel is operated as universla digital DXP
channel.
Data storage mode Synchronization of parameter data of IO-Link devices (storing the parameter of the connected
device in the master).
If the synchronization is not possible, a diagnostic message is displayed (DS_ERR). In this case
the data memory of the master must be deleted:
Select option "11 = deactivated, delete" to delete the data memory of the master
IO-Link devices in accordance with IO-Link specification V1.0 do not support data storage.
When using IO-Link devices with IO-Link V1.0:
Select option "11 = deactivated, delete" to deactivate data storage.
0 0x00 Activated Synchronization of parameter data activated. The ac-
tual data (master or device) serve as the reference
data.
1 0x01 overwrite Synchronization of parameter data activated, the
data in the master serve as reference data.
2 0x02 read in Synchronization of parameter data activated. The
data in the connected IO-Link device serve as refer-
ence data.
3 0x03 Deactivated, clear
Synchronization of parameter data deactivated. The
data set in the master is deleted.
Activate Quick
Start-Up
For fast applications (e.g. tool changing applications) the start-up time of IO-Link devices can
be shortened. The start-up time defined in the IO-Link specification (TSD = Device Detection
Time) is reduced.
0 0x00 No
The start-up time is within the specified range (0.5 s).
All IO-Link devices in accordance with the specifica-
tion can be operated.
1 0x01 Yes The start-up time is reduced to approx. 100 ms. It is
not supported by every IO-Link device. It can thus be
necessary to check if the used IO-Link device starts in
this mode.
Device parameter-
ization via GSD
(GSD)
0 0x00 inactive
The port is generic or is not parameterized.
1 0x01 Active In PROFINET the port is parameterized with a specific
device type from the GSDML-file.