Parameter name Value Meaning Description
Dec. Hex.
Cycle time
0 0x00 Automatic
The lowest cycle time supported by the device is
taken from the table.
16
…
191
0x
10
…
0xBF
1.6…132.8 ms
Settable in steps of 0.8 or 1.6 ms.
255 0xFF Automatic, compatible Compatibility mode The mode solves possible com-
munication problems with sensors of the SGB family
from IFM.
Revision
0 0x00 Automatic
The Master defines the IO-Link revision automatically.
1 0x01 V1.0 IO-Link Revision V 1.0 is used.
Process input data
invalid (PDIN in-
valid)
0 0x00 Diagnostic generated
If the process data are invalid, a respective diagnostic
message is generated.
1 0x01 No diagnostic generated Invalid process data do not cause a diagnostic mes-
sage.
Deactivate dia-
gnostics
Influences the sending of IO-Link-Events from the master to the fieldbus. Depending on the
parameterization, the master transmits Events based on their priority to the fieldbus or not.
0 0x00 No The master transmits all IO-Link Events to the field-
bus.
1 0x01 Notifications The master transmits all IO-Link Events to the fieldbus
except for IO-Link notifications.
2 0x02 Notifications and warn-
ings
The master transmits all IO-Link Events to the fieldbus
except for IO-Link notifications and warnings.
3 0x03 Yes The master doesn't transmit any IO-Link Event to the
fieldbus.
Process inpput
data mapping
(Mapping PDIN)
Optimization of the process data mapping for the used fieldbus: The I/O-Link-data can be
swapped depending on the used fieldbus in order to achieve an optimized data mapping on
the fieldbus side.
PROFINET:
With PROFINET, the parameter is permanently set to 0x00 = direct and cannot be changed.
0 0x00 direct The process data are not swapped.
i.e.: 0x0123 4567 89AB CDEF
1 0x01 Swap 16 bit
The bytes are swapped per word.
i.e.: 0x2301 6745 AB89 EFCD
2 0x02 Swap 32 bit The bytes are swapped per double word.
i.e.: 0x6745 2301 EFCD AB89
3 0x03 swap all All bytes are swapped.
i.e.: 0xEFCD AB89 6745 2301
Process output
data mapping
(Mapping PDOUT)
see above Process input data mapping
Vendor ID 0…65535
0x0000…
0xFFFF
Vendor ID for the port configuration check
Device ID 0…
16777215
0…
0x00FFFFFF
Device ID for the port configuration check
24 bit value