Technical data
Input Assembly Instances 103, 120, 121, 122, 123,124, 125
Number of input bytes 8
Output Assembly Instances 104, 150, 151, 152
Number of output bytes 4
Configuration Assembly Instance 106
Number of configuration bytes 0
PROFINET
PROFINET specification V 2.35
Conformance Class B (RT)
Address assignment DCP
MinCycle Time 1 ms
Fast Start-Up (FSU) < 150 ms
Diagnostics according to PROFINET Alarm Handling
Topology detection Supported
Automatic address setting Supported
Media Redundancy Protocol (MRP) Supported
Digital inputs
Number of channels 4 at C/Q
Input type PNP
Switching threshold EN 61131-2 type 3, PNP
Signal voltage, low level < 5 V
Signal voltage, high level > 11 V
Low level signal current < 1.5 mA
High-level signal current > 2 mA
Input delay 2.5 ms
Digital outputs
Number of channels 4 at C/Q
Output type PNP
Output voltage 24 VDC
Output current per channel Max. < 400 mA
IO-Link
Number of channels 4
IO-Link specification Version 1.1
IO-Link port type Class A at C0…C3
Frame type Supports all specified frame types
Transmission rate 4.8 kbps (COM 1)
38.4 kbps (COM 2)
230.4 kbps (COM 3)
Mounting
Type of mounting Via 2 mounting holes
Standard/Directive conformity
Vibration test According to EN 60068-2-6
Acceleration Up to 20 g