Commissioning
Commissioning the device in EtherNet/IP
62
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Device configuration data
Parameter name Value Meaning
LED-behavior (PWR) at
V2 undervoltage
0 Red PWR-LED constant red at V2 under-
voltage.
1 green PWR-LED is blinking green at V2 under-
voltage.
ETH x Port Setup 0 Auto negotiation The port is set to autonegotiation.
1 100BT/FD Fix setting of the communication para-
meters for the Ethernet port to:
n 100BaseT
n Full duplex
Input assembly instances
EtherNet/IP Con-
nection
Input Assembly Device
status
[byte]
Basic I/O
[byte]
IO-Link
inputs
[byte]
Dia-
gnostics
[byte]
Event data
(byte]
Instance Size
[8 bit]
Exclusive Owner 103 208 2 4 128 10 64
Exclusive Owner
(Omron)
103 208 2 4 128 10 64
IOL 4 IN/4 OUT,
diagnostics
120 32 2 4 16 10 0
IOL 6 IN/6 OUT,
diagnostics
122 40 2 4 24 10 0
IOL 8 IN/8 OUT,
diagnostics
124 48 2 4 32 10 0
IOL 4 IN/4 OUT 121 22 2 4 16 0 0
IOL 6 IN/6 OUT 123 30 2 4 24 0 0
IOL 8 IN/8 OUT 125 38 2 4 32 0 0