Commissioning
Commissioning the device in EtherNet/IP
70
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Output Assembly Instances
EtherNet/IP Con-
nection
Output Assembly Control word
[byte]
DXP outputs
[byte]
IO-Link out-
puts [byte]
VAUX [byte]
Instance Size
[8 bit]
Exclusive Owner 104 134 2 2 128 2
IOL 4 IN/4 OUT 150 22 2 2 16 2
IOL 6 IN/6 OUT 151 30 2 2 24 2
IOL 8 IN/8 OUT 152 38 2 2 32
Instance 104 – Exclusive Owner
The description of the input data can be found in chapter “Parameterizing and configur-
ing” [}110]
Word no. Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Control Word
0x00 - reserved
DXP outputs
0x01 - - - - - - - - - - - - DX3 DX2 DX1 DX0
IO-Link process output data
0x02…
0x11
16 words per port
0x12…
0x21
0x22…
0x31
0x32…
0x41
VAUX Control
0x42 reserved - - - - VAUX pin9 VAUX pin7 VAUX pin5 VAUX pin9