8.1.2 MAINS VOLTAGE 525-690 V
Table 26: The power ratings of VACON
®
100 INDUSTRIAL in mains voltage 525-690 V, 50-60 Hz,
3~
Enclos
ure
size
Drive
type
Loadability Motor shaft power
Low High Max
curre
nt I
s
2s
600 V mains 690 V mains
Contin
uous
curre
nt
I
Lout
[A]
Input
curre
nt I
Lin
[A]
10%
over-
load
curre
nt [A]
Contin
uous
curre
nt
I
Hout
[A]
Input
curre
nt I
Hin
[A]
50%
over-
load
curre
nt [A]
10%
over-
load
40C
[hp]
50%
over-
load
40C
[hp]
10%
over-
load
40C
[kW]
50%
over-
load
40C
[kW]
MR8 0080 80.0 90.0 88.0 62.0 72.0 93.0 124.0 75.0 60.0 75.0 55.0
0100 100.0 106.0 110.0 80.0 89.0 120.0 160.0 100.0 75.0 90.0 75.0
0125 125.0 127.0 137.5 100.0 104.0 150.0 200.0 125.0 100.0 110.0 90.0
MR9 0144 144.0 156.0 158.4 125.0 140.0 187.5 250.0 150.0 125.0 132.0 110.0
0170 170.0 179.0 187.0 144.0 155.0 216.0 288.0 - - 160.0 132.0
0208 208.0 212.0 228.8 170.0 177.0 255.0 340.0 200.0 150.0 200.0 160.0
MR10 0261 261.0 272.0 287.1 208.0 223.0 312.0 416.0 250.0 200.0 250.0 200.0
0325 325.0 330.0 357.5 261.0 269.0 391.5 522.0 300.0 250.0 315.0 250.0
0385 385.0 386.0 423.5 325.0 327.0 487.5 650.0 400.0 300.0 355.0 315.0
0416* 416.0 415.0 457.6 385.0 382.0 577.5 770.0 450.0 300.0 400.0 355.0
MR12 0460 460.0 477.0 506.0 416.0 433.0 624.0 832.0 450.0 400.0 450.0 400.0
0520 520.0 532.0 572.0 460.0 472.0 690.0 920.0 500.0 450.0 500.0 450.0
0590 590.0 597.0 649.0 520.0 527.0 780.0 1040.0 600.0 500.0 560.0 500.0
0650 650.0 653.0 715.0 590.0 591.0 885.0 1180.0 650.0 600.0 630.0 560.0
0750* 750.0 747.0 825.0 650.0 646.0 975.0 1300.0 700.0 650.0 710.0 630.0
0820* 820.0 813.0 902.0 650.0 739.0 975.0 1300.0 800.0 650.0 800.0 630.0
* = These currents are not available when you have both the back channel cooling and du/dt
filter (+CHCB and +PODU).
8.1.3 BRAKE RESISTOR RATINGS
Make sure that the resistance is higher than the set minimum resistance. The power
handling capacity must be sufficient for the application.