9.2 VACON
®
100 FLOW - TECHNICAL DATA
Table 34: The technical data of the VACON
®
100 FLOW AC drive
Technical item or function Technical data
Mains connection
Input voltage U
in
380-500 V, 525-690 V, -10%...+10%
Input frequency 50-60 Hz, -5...+10%
Connection to mains Once per minute or less frequently
Starting delay 8 s (MR8 to MR12)
Mains
Mains types: TN, TT, and IT
Short circuit current: the maximum short circuit
current must be < Icc 65 kA.
Motor connection
Output voltage 0-U
in
Continuous output current
I
L
: Ambient temperature max. +40 °C overload 1.1 x I
L
(1 min/10 min)
Output frequency 0-320 Hz (standard)
Frequency resolution 0.01 Hz
VACON · 124 TECHNICAL DATA, VACON® 100 FLOW
9
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/