Table 11: Drive fuses, 525-690 V, Mersen (IEC)
Enclosure
size
Type I
L
[A] Catalogue number of the
fuse
Fuse
rating
[A]
Number
of fuses
needed
Fuse
size
Minimum
prospective
short
circuit
current [A]
MR8
0080 7 80 NH1UD69V125PV 125 3 1 500
0100 7 100 NH1UD69V160PV 160 3 1 700
0125 7 125 NH1UD69V200PV 200 3 1 1000
MR9
0144 7 144 NH1UD69V315PV 315 3 1 2000
0170 7 170 NH1UD69V350PV 350 3 1 2400
0208 7 208 NH1UD69V400PV 400 3 1 2800
MR10
0261 7 261 NH2UD69V400PV 400 3 2 2800
0325 7 325 NH2UD69V500PV 500 3 2 3300
0385 7 385 NH2UD69V630PV 630 3 2 5000
0416 7 416 NH3UD69V900PV 900 3 3 7100
MR12
0460 7 460 NH2UD69V400PV 400 6 2 2400
0520 7 520 NH2UD69V450PV 450 6 2 2800
0590 7 590 NH2UD69V500PV 500 6 2 3300
0650 7 650 NH2UD69V550PV 550 6 2 4000
0750 7 750 NH2UD69V630PV 630 6 2 5000
0820 7 820 NH3UD69V900PV 900 6 3 7100
VACON · 56 POWER CABLING
5
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/