16(80) Technical data vacon
Vacon Oyj Telephone: +358-201-2121 Fax: +358-201-212 205
24-hour support: +358-40-8371 150 Email: vacon@vacon.com
4
4.3 Technical data
Input voltage U
in
208240V; 380500V
Input frequency 4566 Hz
Mains
connection
Connection to mains Once per minute or less (normal case)
Output voltage 0U
in
Continuous output current I
H
: Ambient temperature max. +50ºC,
overload 1.5 x IH (1min/10min)
I
L
: Ambient temperature max. +40ºC,
overload 1.1 x IL (1min/10min)
Starting torque 150% (Low overload); 200% (High overload)
Starting current 2 x IH 2 secs every 20 secs, if output frequency <30Hz
and temperature of heatsink <+60ºC
Output frequency 0320 Hz
Motor
connection
Frequency resolution 0,01 Hz
Control method Frequency Control U/f
Open Loop Sensorless Vector Control
Switching frequency
(See parameter 2.6.8)
1...16 kHz; Factory default 6 kHz
Frequency reference
Analogue input
Keypad reference
Resolution 0.1% (10bit), accuracy ±1%
Resolution 0.01 Hz
Field weakening point 30320 Hz
Acceleration time 03000 sec
Deceleration time 03000 sec
Control
characteristrics
Braking torque DC-brake: 30%*TN (without brake option)
Ambient operating
temperature
10°C (no frost)+50°C: I
H
10°C (no frost)+40°C: I
L
Storage temperature 40°C+70°C
Relative humidity 095% RH, non-condensing, non-corrosive,
no dripping water
Air quality:
- chemical vapours
- mechanical particles
IEC 721-3-3, unit in operation, class 3C2
IEC 721-3-3, unit in operation, class 3S2
Altitude 100% load capacity (no derating) up to 1000m
1-% derating for each 100m above 1000m; max. 3000m
Vibration:
EN50178/EN60068-2-6
5...150 Hz
Displacement amplitude 1(peak) mm at 5...15.8 Hz
Max acceleration amplitude 1 G at 15.8...150 Hz
Shock
EN50178, IEC 68-2-27
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in package)
Ambient
conditions
Enclosure class IP20; MF2 and MF3. IP21; MF4 and bigger
Immunity Complies with EN50082-1, -2, EN61800-3
EMC
Emissions Coded series complies with EN61800-3, restricted
distribution.
With an external filter attached compliance with EN50081-
1, -2 and EN61800-3, unrestricted distribution
Technical data (continues on next page)