vacon Control keypad 69(80)
Vacon Oyj Telephone: +358-201-2121 Fax: +358-201-212 205
24-hour support: +358-40-8371 150 Email: vacon@vacon.com
7
7.3.7 Expander board menu (E7)
The Expander board menu makes it possible for the user 1) to see which expander board is
connected to the control board and 2) to reach and edit the parameters associated with the
expander board.
Enter the following menu level (E#) with the Menu button right. You can view and edit the
parameter values in the same way as described in chapter 7.3.2. See Table 7-12.
Expander board parameters
Code Parameter Min Max Default Cust Selections
P7.1.1.1 AI1 mode 1 4 3
1=0…20 mA
2=4…20 mA
3=0…10 V
4=2…10 V
P7.1.1.2 AI2 mode 1 2 1
1=0…20 mA
2=4…20 mA
P7.1.1.3 AO1 mode 1 2 1
1=0…20 mA
2=4…20 mA
Table 7-12. Expander board parameters (board NXOPTA1)
7.4 Further keypad functions
The Vacon NXL control keypad embodies additional application-related functions. See Vacon
Multicontrol Application Manual for more information.