EasyManua.ls Logo

Vacon NXL 0023 5 - Control Terminal Signals

Vacon NXL 0023 5
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
vacon Cabling and connections 37(80)
Vacon Oyj Telephone: +358-201-2121 Fax: +358-201-212 205
24-hour support: +358-40-8371 150 Email: vacon@vacon.com
6
6.2.3
Control terminal signals
Terminal Signal Technical information
1
+10 Vref Reference voltage Maximum current 10 mA
2
AI1+ Analogue input,
voltage
(MF4 and bigger: voltage or current)
Selection V or mA with jumper block X4 (see page 38):
Default: 0– +10V (Ri = 200 k)
0– 20mA (Ri = 250 )
3
AI1– Analogue input common Differential input if not connected to ground;
Allows ±20V differential mode voltage to GND
4
AI2+ Analogue input, voltage or
current
Default: 0– 20mA (Ri = 250 )
5
AI2– Analogue input common Differential input;
Allows ±20V differential mode voltage to GND
6
24 Vout 24V auxiliary voltage ±10%, maximum current 100 mA
7
GND I/O ground Ground for reference and controls
8
DIN1 Digital input 1
9
DIN2 Digital input 2
10
DIN3 Digital input 3
R
i
= min. 5k
11
GND I/O ground Ground for reference and controls
18
AO1+ Analogue signal (+output)
19
AO1– Analogue output common
Output signal range:
Current 0(4)–20mA, R
L
max 500 or
Voltage 0—10V, R
L
>1k
A
RS 485 Serial bus
B
RS 485 Serial bus
21
RO1/1
22
RO1/2
23
RO1/3
Relay output 1 Switching capacity: 24VDC/8A
250VAC/8A
125VDC/0,4A
Relay output terminals are galvanically isolated from the
I/O ground
Table 6-6. Control I/O terminal signals