7.3.3 Keypad control menu (K3)
In the Keypad Controls Menu, you can choose the control place, edit the frequency reference and
change the direction of the motor. Enter the submenu level with the Menu button right.
Parameters in
Menu K3
Selections
P3.1 = Selection of control
place
1 = I/O terminals
2 = Keypad
3 = Fieldbus
R3.2 = Keypad reference
P3.3 = Keypad direction
0 = Forward
1 = Reverse
P3.4 = Stop button activation
0 = Limited function of Stop
button
1 = Stop button always
enabled
R3.5 = PID reference 1
R3.6 = PID reference 2
7.3.3.1 Selection of control place
There are three different places (sources) which the frequency converter can be controlled from. For
each control place, a different symbol will appear on the alphanumeric display:
Control place Symbol
I/O terminals
I/O term
Keypad (panel)
Keypad
Fieldbus
Bus/Comm
Change the control place by entering the edit mode with the Menu button right. The options can then be
browsed through with the Browser buttons. Select the desired control place with the Enter button. See the
diagram below. See also 0 above.
Figure 7-7. Selection of control place