vacon Cabling and connections 23(80)
Vacon Oyj Telephone: +358-201-2121 Fax: +358-201-212 205
24-hour support: +358-40-8371 150 Email: vacon@vacon.com
5
C
A
NK5
_
2
D
B
A
B
5.2 Cooling
The cooling method in NXL drive is either convection or air cooling with a cooling fan. The cooling
method for lower power ranges (frame MF2 and lower powers of MF3) is a convection type
cooling. Forced air flow cooling is used for frames MF4, MF5, MF6 and higher powers of MF3.
Enough free space shall be left above and below the frequency converter to ensure sufficient air
circulation and cooling. You will find the required dimensions for free space in the table below.
Type Dimensions [mm]
AB C D
0001-0005 NXL 5 100 50
0007-0012 NXL 5 20 20 100 50
0016-0032 NXL 5 20 20 120 60
Table 5-4. Mounting space dimensions
Figure 5-7. Installation space
A = clearance around the freq. converter (see also B)
B = distance from one frequency converter to another or
distance to cabinet wall
C = free space above the frequency converter
D = free space underneath the frequency converter