Fieldbus protocol (P6.10.2)
With this function you can select the fieldbus communications protocol.
0 = Not used
1 = Modbus protocol
Slave address (P6.10.3)
Set here the slave address for the modbus protocol. You can set any address between 1 and 255.
Baud rate (P6.10.4)
Selects the baud rate used with the modbus communication.
0 = 300 baud
1 = 600 baud
2 = 1200 baud
3 = 2400 baud
4 = 4800 baud
5 = 9600 baud
6 = 19200 baud
7 = 38400 baud
8 = 57600 baud
Stop bits (P6.10.5)
Set the number of stop bits used in Modbus communication
0 = 1 stop bit
1 = 2 stop bits
Parity type (P6.10.6)
Here you can select the type of parity checking used with the modbus communication.
0 = None
1 = Even
2 = Odd
Communication time-out (P6.10.7)
If communication between two messages is broken for a longer time than that defined by this parameter, a
communication error is initiated. If the value of this parameter is 0, the function is not used.
0 = Not used
1 = 1 second
2 = 2 seconds, etc