vacon Commissioning 75(80)
Vacon Oyj Telephone: +358-201-2121 Fax: +358-201-212 205
24-hour support: +358-40-8371 150 Email: vacon@vacon.com
8
P2.1.16
Analogue output
function
012 1
307
0=Not used
1=Output freq. (0—f
max
)
2=Freq. reference (0—f
max
)
3=Motor speed (0—Motor
nominal speed)
4=Output current (0—I
n
otor
)
5=Motor torque (0—T
nMotor
)
6=Motor power (0—P
nMotor
)
7=Motor voltage (0--U
nMotor
)
8=DC-link volt (0—U
nMotor
)
9=PI controller ref. value
10=PI contr. act. value 1
11=PI contr. error value
12=PI controller output
P2.1.17 DIN2 function 0 9 1
319
0=Not used
1=Start Reverse
2=Reverse
3=Stop pulse
4=External fault, cc
5=External fault, oc
6=Run enable
7=Preset speed 2
8= Motor pot. UP (cc)
9= Disable PID (Direct freq.
reference)
P2.1.18 DIN3 function 0 12 6
301
0=Not used
1=Reverse
2=External fault, cc
3=External fault, oc
4=Fault reset
5=Run enable
6=Preset speed 1
7=Preset speed 2
8=DC-braking command
9=Motor pot. UP (cc)
10=Motor pot. DOWN (cc)
11=Disable PID (PID
control selection)
12=PID Keypad ref. 2
selection
P2.1.19 Preset speed 1 0,00 Par. 2.1.2 Hz 10,00
105
P2.1.20 Preset speed 2 0,00 Par. 2.1.2 Hz 50,00
106
P2.1.21 Automatic restart 0 1 0
731
0=Not used
1=Used
P2.1.22 Parameter conceal 0 1 1
115
0=All parameters visible
1=Only group b21 visible
Table 8-2. Basic parameters B2.1