80(80) Board NXOPTAA vacon
Vacon Oyj Telephone: +358-201-2121 Fax: +358-201-212 205
24-hour support: +358-40-8371 150 Email: vacon@vacon.com
10
I/O terminals on NXOPTAA
Terminal Parameter
setting
Description
X3
1 +24V Control voltage output; voltage for switches etc, max. 150 mA
2 GND Ground for controls, e.g for +24 V and DO
3 DIN1 DIGIN:x.1 Digital input 1
4 DIN2 DIGIN:x.2 Digital input 2
5 DIN3 DIGIN:x.3 Digital input 3
6 DO1 DIOUT:x.1 Open collector output, 50mA/48V
X5
24
25
26
RO1/NC
RO1/C
RO1/NO
DIOUT:x.2 Relay output 1 (NO)
Switching capacity: 24VDC/8A
250VAC/8A
125VDC/0,4A
Table 10-1. I/O terminals of board NXOPTAA
Note! The +24 V control voltage terminal can also be used to power the control module (but not
the power module).