Table 19: The minimum clearances around the AC drive
Drive type Dimensions [mm] Dimensions [inch]
A B C D A B C D
0003 2-0012 2
0003 5-0012 5
20 20 100 50 0.79 0.79 3.94 1.97
0017 2-0031 2
0016 5-0031 5
20 20 120 60 0.79 0.79 4.72 2.36
0048 2-0061 2
0038 5-0061 5
0004 6-0034 6
30 20 160 80 1.18 0.79 6.30 3.15
0075 2-0114 2
0072 5-0105 5
0041 6-0052 6
80 80 300 100 3.15 3.15 11.81 3.94
0140 2-0205 2
0140 5-0205 5
0062 6-0100 6
80 * 80 300 200 3.15 3.15 11.81 7.87
0261 2-0300 2
0261 5-0300 5
0125 6-0208 6
50 80 400
250
(350**)
1.97 3.15 15.75
9.84
(13.78**)
* = To change the fan with the motor cables connected, the necessary clearance on the 2
sides of the drive is 150 mm (5.91 inch).
** = The minimum clearance to change the fan.