5.3.1 CABLE AND FUSE SIZES FOR 208-240 V AND 380-500 V, FR4 TO FR9
Table 24: The cable and fuse sizes for Vacon
®
NXS and NXP
Frame Type I
L
[A]
Fuse
(gG/gL) [A]
Mains, motor
and brake
resistor cable
Cu [mm
2
]
Terminal cable size
Mains cable
terminal
[mm
2
]
Grounding
terminal
[mm
2
]
FR4
0003 2—0008 2
0003 5—0009 5
3–8
3–9
10 3*1.5+1.5 1–4 1–4
0011 2—0012 2
0012 5
11–12
12
16 3*2.5+2.5 1–4 1–4
FR5
0017 2
0016 5
17
16
20 3*4+4 1–10 1–10
0025 2
0022 5
25
22
25 3*6+6 1–10 1–10
0031 2
0031 5
31
31
35 3*10+10 1–10 1–10
FR6
0048 2
0038 5—0045 5
48
38–45
50 3*10+10
2.5–50 Cu
6–50 Al
2.5–35
0061 2
0061 5
61 63 3*16+16
2.5–50 Cu
6–50 Al
2.5–35
FR7
0075 2
0072 5
75
72
80 3*25+16
2.5–50 Cu
6–50 Al
6–70
0088 2
0087 5
88
87
100 3*35+16
2.5–50 Cu
6–50 Al
6–70
0114 2
0105 5
114
105
125 3*50+25
2.5–50 Cu
6–50 Al
6–70
POWER CABLING VACON · 47
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM