Loading...
Table 24: The cable and fuse sizes for Vacon
®
NXS and NXP
Frame Type I
L
[A]
Fuse
(gG/gL) [A]
Mains, motor
and brake
resistor cable
Cu [mm
2
]
Terminal cable size
Mains cable
terminal
[mm
2
]
Grounding
terminal
[mm
2
]
FR8
0140 2
0140 5
140 160 3*70+35 25–95 Cu/Al 6–95
0170 2
1)
0168 5
1)
168 200 3*95+50
95–185
Cu/Al
6–95
0205 2
0205 5
205 250 3*150+70
95–185
Cu/Al
6–95
FR9
0261 2
1)
0261 5
1)
261 315
3*185+95 or
2*(3*120+70)
95–185
Cu/Al
6–95
0300 2
1)
0300 5
1)
300 315 2*(3*120+70)
95–185
Cu/Al
6–95
1)
= Use cables with a +90 °C (194 °F) heat resistance to obey the UL standards.