EasyManua.ls Logo

Vacon nxs - CABLE AND FUSE SIZES FOR 500-690 V, FR10 TO FR11

Vacon nxs
165 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.3.4 CABLE AND FUSE SIZES FOR 500-690 V, FR10 TO FR11
Table 30: The cable and fuse sizes for Vacon
®
NXS and NXP
Frame Type I
L
[A]
Fuse
(gG/gL) [A]
Mains, motor and brake
resistor cable
1)
[mm
2
]
Number of
supply
cables
Number of
motor
cables
FR10
0261 6 261 315 (3 pcs)
Cu: 3*185+95
Al: 2*(3*95Al+29Cu)
Even/Odd Even/Odd
0325 6 325 400 (3 pcs)
Cu: 2x(3*95 + 50)
Al: 2*(3*150Al+41Cu)
Even/Odd Even/Odd
0385 6 385 400 (3 pcs)
Cu: 2*(3*120+70)
Al: 2*(3*185Al+57Cu)
Even/Odd Even/Odd
0416 6 416 500 (3 pcs)
Cu: 2*(3*150+70)
Al: 2*(3*185Al+57Cu)
Even/Odd Even/Odd
FR11
0460 6 460 500 (3 pcs)
Cu: 2*(3*150+70)
Al: 2*(3*240Al+72Cu)
Even/Odd Even/Odd
0502 6 502 630 (3 pcs)
Cu: 2*(3*185+95)
Al: 2*(3*300Al+88 Cu)
Even/Odd Even/Odd
0590 6 590 315 (6 pcs)
Cu: 2*(3*240+120)
Al: 4*(3*120Al+41Cu)
Even Even/Odd
1)
uses a correction factor 0.7
POWER CABLING VACON · 55
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM