Dedicated Outdoor Air Unit 15
Phase Monitor
The unit control circuitry includes a phase monitor that 
constantly checks for phase reversal, phase imbalance, 
loss of phase or a power brownout. When it detects a 
fault, it cuts off the 24 VAC that goes to the low voltage 
terminal strip, thereby shutting off all motors.
Variable Frequency Drive (VFD)
If a VFD was provided and installed at the factory, it has 
been pre-set to control the speed of the blower motor 
for optimum performance. The motor speed needs to be 
verified during test and balance of the unit. 
If the system was configured for Constant Air Volume 
(CAV), the VFD will operate in an ON/OFF fashion 
and the speed of the motor will not change. If the 
system was configured for Variable Air Volume (VAV), 
the microprocessor will constantly monitor operating 
conditions and provide a signal to the VFD, changing 
the VFD output as needed.
The VFD may alternatively be connected to an external 
signal such as provided by a BMS and be operated by a 
2-10 VDC or a 4-20 mA input.
Supply Fan VFD Sequence
Optional Room CO
2
 Sensor:  The microprocessor will 
modulate the supply fan based on a comparison of the 
CO
2
 set point to the actual CO
2
 levels reported from 
the sensor. Mechanical high static protection cutoffs 
must be installed by others to protect the system and 
equipment from over-pressurization.
Optional Duct Static Pressure Sensor:  The 
microprocessor will modulate the supply fan based 
on a comparison of the duct static pressure set point 
to the actual duct static pressure level reported from 
the sensor. Mechanical high static protection cutoffs 
must be installed by others to protect the system and 
equipment from over-pressurization. The manufacturer 
does not assume responsibility for this.
Optional Building Static Pressure Sensor:  The 
supply fan is modulated based upon the signal from a 
building static pressure sensor. The microprocessor will 
modulate the supply fan based on a comparison of the 
building static pressure set point to the actual building 
static pressure level reported from the sensor.
Optional Single Zone VAV:  The microprocessor will 
use a space mounted temp sensor to vary heating and 
cooling capacity and the airflow delivered by the fan to 
maintain room-air temp at a desired set point.
Optional 0-10 VDC by others to VFD:  Supply fan is 
modulated by a  0-10 VDC, field-provided by others.
Component Operation
Exhaust Fan VFD Sequence
Optional Building Static Pressure Sensor:  The 
exhaust fan is modulated based upon the signal from 
a building static pressure sensor. The microprocessor 
will modulate the exhaust fan based upon a comparison 
of the building static pressure level reported from the 
sensor.
Optional Outdoor Air Damper Tracking:  The 
microprocessor will proportionally modulate the exhaust 
fan based upon the outdoor air damper position.
Optional Supply Tracking:  The microprocessor will 
proportionally modulate the exhaust fan based upon the 
supply fan.
Optional 0-10 VDC by Others to VFD:  The supply fan 
is modulated by a 0-10 VDC provided by others in the 
field.
Outdoor Air and Recirculated (Recirc) Air 
Damper Sequence
Optional Room CO
2
 Sensor:  The microprocessor 
will proportionally modulate the OA/RA dampers based 
upon a comparison of the CO
2
 set point to the actual 
CO
2
 level reported from the sensor. As the CO
2
 level 
rises, the controller will proportionally modulate the 
outdoor air damper open, between the minimum and 
maximum OA position.
Optional Building Pressure:  The OA/RA dampers 
will modulate based upon the signal from a building 
static pressure sensor. The controller will modulate 
the dampers, between the minimum and maximum OA 
positions, based upon a comparison of the building 
static pressure set point to the actual building static 
pressure level reported from the sensor.
Exhaust Fan Only Power
The exhaust fan will have a dedicated power circuit 
where in the case of a power outage, the exhaust fan 
will still run. A phase monitor will detect an outage or 
power loss and open the contact, disconnecting all 
power to the unit and controller. An external signal will 
need to be sent to a relay to power the exhaust fan, 
enabling  the fan to run at a maximum speed. This 
sequence is NOT to be used for high temperature 
exhaust applications.
Vapor Tight Lights
Vapor tight lights provide light to each of the 
compartments in the energy recovery unit. The lights 
are wired to a junction box mounted on the outside of 
the unit. The switch to turn the lights on is located in 
the unit control center. The switch requires a separate 
power source to allow for power to the lights when the 
unit main disconnect is off for servicing.
Optional Component Operation