Dedicated Outdoor Air Unit 19
Factory-Installed Refrigeration System Components
Packaged DX Cooling with Three Way Hot Gas Reheat and Hot Gas Bypass
  1. Compressor
  2.  High Limit Pressure Switch 
The switch opens when refrigerant pressure 
increases above the set point in the discharge line. 
A manual reset is then required.
  3.  Hot Gas Reheat Valve (optional) 
Units equipped with a reheat coil use a three-
way valve with actuator to control the supply 
air discharge temperature of the unit during 
dehumidification mode. The unit controller provides 
a 0-10 VDC signal to control the amount of reheat 
to meet the supply temperature set point
  4.  Hot Gas Reheat Coil (Optional)
  5.  Hot Gas Reheat Check Valve (Optional)
  6.  Condenser Fans
  7.  Condensing Coil
 8.  Liquid Receiver (Optional)
  9.  Liquid Line Filter Drier
 10.  Sight  Glass
 11.  Fan Cycle Switch(es) 
The switch(es) open or close based on liquid 
refrigerant pressure to control the condensing fans 
to maintain liquid pressure.
 12.  Thermostatic Expansion Valve (TVX) 
Each unit is equipped with a TVX on each 
refrigerant circuit. The valve controls the flow of 
liquid refrigerant entering the evaporator coil by 
maintaining a constant, factory-set superheat of 
10°F. The valve is adjustable and is located on the 
side of the evaporator coil and can be accessed 
through the coil access panel.
 13.  Evaporative  Coil
 14.  Low Limit Pressure Switch 
The switch is installed on the suction line and 
disables the DX system when the suction pressure 
drops below the set point. The switch will auto reset 
when the pressure rises above the auto-reset set 
point.
 15.  Service Access Ports
 16.  Hot Gas Bypass Manual Shut Off Valve (Optional) 
Used to disable hot gas bypass for service and 
troubleshooting procedures.
 17.  Hot Gas Bypass Valve (Optional) 
On units equipped with hot gas bypass, hot gas 
from the compressor is injected into the liquid line 
of the evaporator coil after the TVX.
    Valve Adjustment - To adjust the valve, connect 
a pressure gauge to the suction line and block the 
entering air to the evaporator coil. The valve should 
begin to open when the suction pressure drops to 
approximately 115 PSIG for R-410A (the valve will 
feel warm to the touch). Adjustments are made by 
first removing the cap on the bottom of the valve 
and then turning the adjusting stem clockwise to 
increase the setting pressure (counterclockwise 
to decrease). Allow several minutes between 
adjustments for the system to stabilize. When 
adjustment is complete, replace the cap on the 
valve.
 18.  Pressure Gauge & Transducer (Optional EC 
condenser fans only)
 See Optional Electronically Commutated (EC) 
Condenser Fans under the component operation.