Dedicated Outdoor Air Unit 23
Pre-Start-Up Checklist
o  Remove any foreign objects that are located in the 
unit.
o  Check all fasteners, set-screws, and locking collars 
on the fans, bearings, drives, motor bases and 
accessories for tightness.
o  Rotate the fan wheels and energy recovery wheels 
by hand and ensure no parts are rubbing. 
o  Verify diameter seal settings on the energy recovery 
wheel.
o  Filters can load up with dirt during building 
construction. Replace any dirty pleated filters and 
clean the aluminum mesh filters in the intake hood.
o  Verify that non-motorized dampers open and close 
properly.
o  Check the tightness of all factory wiring 
connections.
o  Verify proper drain trap installation.
o  Check condensing fans for any damage or 
misalignment. Spin the blades and make sure they 
don’t contact any parts and are free turning without 
any resistance.
o  Look over the piping system. 
o  Inspect all coils within the unit. Fins may get 
damaged in transit or during construction. Carefully 
straighten fins with a fin comb.
Electrical
oDisconnect and lock-out all power switches.
o  Verify control wire gauge. 
o  All field-mounted sensors and instruments are 
installed and wired.
o  Unit controls are off.
o  Electrical service matches unit voltage.
o  Electrical field wiring is complete.
o  All electrical connections are tightened.
o  Compressor and motor breakers or fuses are open 
(disabled).
o  Main power is wired to the disconnect.
o  Discharge air sensor is installed per wiring 
instructions.
o  Space temperature and humidity sensors are 
installed per if selected with unit.
Compressors
o  This unit contains an external crankcase heater for 
each standard or digital scroll compressor. The 
variable speed compressor uses internal stator 
heating. Each compressor needs power supplied to 
it 24hours prior to start-up. If start-up is scheduled 
in 24 hours, unlock the disconnect power and 
energize unit.
oCompressor shipping brackets are removed if 
provided.
SPECIAL TOOLS REQUIRED
•  Voltage Meter (with wire probes)
•  Amperage Meter
•  Pressure Gauges – (refrigerant)
• Tachometer
• Thermometer
•  Incline manometer or equivalent
Start-Up Procedure
The unit will be in operational mode during start-up. Use 
necessary precautions to avoid injury. All data must be 
collected while the unit is running. 
o  Make sure Pre-Start-Up checklist is complete.
o  Jumper R to G, R to Y1, and R to Y2 (if applicable) 
on the control board.
o  Turn the disconnect on. After 3 minutes compressors 
will come on. Make sure all fans and compressors 
are rotating the correct direction.
o  Allow the unit to run until the refrigerant system 
stabilizes. Approximately 1-2 minutes.
Voltage Imbalance
In a 3-phase system, excessive voltage imbalance 
between phases will cause motors to overheat and 
eventually fail. Maximum allowable imbalance is 2%. 
To determine voltage imbalance, use recorded voltage 
measurements in this formula.
Key:   V1, V2, V3 = line voltages as measured 
  VA (average) = (V1 + V2 + V3) / 3 
  VD = Line voltage (V1, V2 or V3) that  
  deviates farthest from average (VA)
Formula:  % Voltage Imbalance = [100 x (VA-VD)] /VA
Start-Up Unit
IG Furnace
o  If there is an indirect gas-fired furnace in this unit, 
refer to the manual provided with this unit for Pre-
Start-Up information.
o  Gas piping is complete and gas lines are purged.
o  Gas venting is in place.
Hot Water/Chilled Water Coils
o  Chilled water piping system is complete.
o  Hot water piping system is complete.
o  Control valves are installed, wired, and operating 
properly.
o  Water coils are balanced to design GPM.
o  Water system is free of air.