Dedicated Outdoor Air Unit8
Additional Clearances for  
Packaged DX Units
Packaged DX units require additional clearance 
because they must have unrestricted air movement 
around the condenser coil and condenser fans. Hot air 
is being discharged from the condenser fans during 
operation. Enough clearance must be provided to 
avoid recirculation or coil starvation. When equipped 
with condenser coils, the unit should never be placed 
under an overhang or inside a building. A minimum of 
48inches above the condenser fans is acceptable, but 
unobstructed is strongly recommended.  
END VIEW OF MAKE-UP AIR UNIT
WITH PACKAGED DX
Minimum 48 inches clearance
Minimum 18 inches 
clearance
Condenser Coil
Condenser Fans
End view of rooftop unit with Packaged DX
Installation
Additional Clearances for  
Air Source Heat Pump
Air-source heat pump units require additional clearance 
because they must have unrestricted air movement 
around the outdoor coil and outdoor fans. Enough 
clearance must be provided to avoid recirculation or 
coil starvation. Air-source heat pump units should 
never be placed under an overhang or inside a building. 
A minimum of 48-inches above the outdoor fans is 
acceptable, but unobstructed is strongly recommended.
IMPORTANT
Air-source heat pumps are equipped with a defrost 
cycle to remove ice from the outdoor coil. During 
defrost cycles, melted water may drip from the bottom 
of the refrigeration section under the outdoor coil. 
In cold climates, proper drainage/heat tape must be 
installed under the outdoor coil to prevent the buildup 
of ice on the roof.
Handling Concerns for 
Packaged DX or Air-Source Heat Pump
Units with PDX or ASHP have a system that is 
pressurized with refrigerant. If damage occurs, the 
refrigerant could leak into the atmosphere or cause 
bodily harm due to the extreme cold nature of 
expanding refrigerant. Use protective equipment such 
as gloves and safety glasses to minimize or prevent 
injury in case of a system leak during installation.
Before Lifting 
Before lifting, be sure that all shipping materials have 
been removed from the unit.
Vestibule
Determine whether or not the unit has a vestibule that 
must be field-attached to the side of the unit. Vestibules 
are shipped assembled but detached from the unit. 
They have lifting lugs on them so they can also be lifted 
by crane, but the installed location of the unit may make 
it preferable to install the vestibule on the unit prior to 
lifting.
Field Power Access
Determine where high voltage and low voltage wiring is 
to be brought into the cabinet. If wiring is to be brought 
into the cabinet through the floor, see Alternate Supply 
Entry Locations in this manual. If unit is to be installed 
on a roof, cut access openings in the roof deck as 
needed.