Dedicated Outdoor Air Unit 21
  1. Compressor
  2.  High Limit Pressure Switch 
The switch opens when refrigerant pressure 
increases above the set point in the discharge line. 
A manual reset is then required.
  3.  Hot Gas Reheat Valve (optional) 
Units equipped with a reheat coil use a three-
way valve with actuator to control the supply 
air discharge temperature of the unit during 
dehumidification mode. The unit controller provides 
a 0-10 VDC signal to control the amount of reheat 
to meet the supply temperature set point
  4.  Hot Gas Reheat Coil (Optional)
  5.  Hot Gas Reheat Check Valve (Optional)
  6.  Outdoor Fans
  7.  Outdoor Coil
 8.  Refrigeration Accumulator
  9.  Liquid Line Filter Drier
 10.  Sight  Glass
 11.  Four Way Reversing Valve 
Each compressor circuit is equipped with a 
reversing valve to reverse the direction of refrigerant 
flow, switching the unit between heating and 
cooling mode.
 12.  Electronic Expansion Valve (EXV) or 
Thermostatic Expansion Valve (TXV) 
An expansion valve is provided on each refrigerant 
circuit. This valve controls the flow of liquid 
refrigerant entering the indoor and outdoor coils 
by maintaining a constant superheat. The TXV is 
adjustable. Both the EXV and TXV are located on 
the side of the outdoor coil and can be accessed 
through the refrigeration system access panel.  
 13.  Indoor  Coil
 14.  Low Limit Pressure Switch 
The switch is installed on the suction line and 
disables the DX system when the suction pressure 
drops below the set point. The switch will auto reset 
when the pressure rises above the auto-reset set 
point.
 15.  Service Access Ports 
Typical port locations are shown. Additional valves 
may be present in the system.
 16.  Refrigerant Pressure Transducers
Factory-Installed Refrigeration System Components