Dedicated Outdoor Air Unit22
DANGER
Electric shock hazard. Can cause injury or death. 
Before attempting to perform any service or 
maintenance, turn the electrical power to unit to OFF 
at disconnect switch(es). Unit may have multiple 
power supplies.
CAUTION
Use caution when removing access panels or other 
unit components, especially while standing on a 
ladder or other potentially unsteady base. Access 
panels and unit components can be heavy and serious 
injury may occur.
CAUTION
Do not operate without the filters and birdscreens 
installed. They prevent the entry of foreign objects 
such as leaves, birds, etc.
CAUTION
Do not run unit during construction phase. Damage to 
internal components may result and void warranty.
WARNING
•  Unit was factory tested. All blowers, fans, 
and compressors are set-up to run correctly 
when supplied power. If any one fan is running 
backwards or the compressor is making loud 
noises, immediately turn off the power. Switch two 
leads on the incoming power to the disconnect. 
This will ensure proper operation of the unit. Failure 
to comply may damage the compressors and void 
the warranty.
•  Do not jumper any safety devices when operating 
the unit. This may damage components within or 
cause serious injury or death.
•  Do not operate compressor when the outdoor 
temperature is below 40ºF.
•  Do not short-cycle the compressor. Allow 
5 minutes between “on” cycles to prevent 
compressor damage.
•  DX system is charged with refrigerant. Start-up 
must be performed by EPA Certified Technician.
Start-Up Unit
Every installation requires a comprehensive start-up 
to ensure proper operation of the unit. As part of that 
process, the following checklist must be completed and 
information recorded. Starting up the unit in accordance 
with this checklist will not only ensure proper operation, 
but will also provide valuable information to personnel 
performing future maintenance. Should an issue arise 
which requires factory assistance, this completed 
document will allow unit experts to provide quicker 
resolve. Qualified personnel should perform start-up to 
ensure safe and proper practices are followed.
Unit Model No.  ___________________________________
Unit Serial No.  ____________________________________
Energy Wheel Date Code  __________________________
Compressor 1 Model No.  __________________________
Compressor 2 Model No.  __________________________
Compressor 3 Model No.  __________________________
Compressor 4 Model No.  __________________________
Start-Up Date  ____________________________________
Start-Up Personnel Name  __________________________
Start-Up Company  ________________________________
Phone Number  ___________________________________
WARNING
Prior to starting up the unit, power must be energized 
for 24 hours without a call for cool to allow the 
compressor crankcase heaters time to boil off any 
liquid refrigerant present in the compressor.