Dedicated Outdoor Air Unit16
Optional Component Operation
Electronically Commutated (EC) 
Condenser Fans with Standard Scroll or 
Digital Scroll Compressors
The EC condenser fan will 
modulate up and down to 
maintain the highest liquid 
line pressure. The factory 
set points are: Set (left 
dial): 23 barg; Diff (right 
dial): 5 barg.
Fan operation with these 
set points are as follows. 
The fan will be at max 
speed (~1140 rpm) when 
the highest liquid line 
saturation temperature 
is 118°F (410psig, 28 
barg). The fan remains at 
max speed if the pressure is higher than 410psig (28 
barg). The fan will be at min speed (~180rpm) when 
the highest liquid line saturation temperature is 105°F 
(340 psig, 23 barg). Below this pressure, the fan will be 
off. The fan modulates linearly between the min and 
max speeds. If unit is selected with inverter compressor 
or air-source heat pump, reference the supplemental 
Reference Guide for Microprocessor Controller.
Air-Source Heat Pump
Operating Conditions and Limitations
To operate in Cooling mode, the following conditions 
must be true:
  1.  Supply air temperature above minimum low supply 
temperature limit (35°F)
  2.  Outside air temperature above the cooling ambient 
lockout (55°F, adj.)
To operate in Heating mode, the following conditions 
must be true:
  1.  Supply air temperature below maximum high 
supply temperature limit (120°F)
  2.  Supply air temperature above 35°F
  3.  Outside air temperature above the low ambient 
lockout (10°F, adj.)
For more information on air-source heat pump 
operation, reference the supplemental Reference Guide 
for Microprocessor Controller.
Set (left dial): 23 barg;  
Diff (right dial): 5 barg
IMPORTANT
Air-source heat pumps are equipped with a defrost 
cycle to remove ice from the outdoor coil.  During 
defrost cycles, melted water may drip from the 
bottom of the refrigeration section under the outdoor 
coil.  In cold climates, proper drainage/heat tape must 
be installed under the outdoor coil to prevent the 
buildup of ice on the roof.
IMPORTANT
Melted water from snow accumulation on the unit 
roof can be sucked into outdoor fans, resulting in ice 
formation on fan blades under certain conditions.  
Remove snow accumulation from the unit roof and 
outdoor coil section after snow storms.