3.3.0.1 Terminal block wiring
Reader
Terminal
Block
Recommended
Wiring colour
Controller
Input PIN
Signal Information
SENSE White SENSE For Entry readers connect the reader SENSE cable or terminal to
the SENSE input pin. For Exit readers, do not use this input.
CLOCK/D1 Green CLOCK/D1 This is the clock or strobe signal input on the ACTpro 1520/1500.
DATA/D0 Blue DATA/D0 This is the Data input.
+12V/24V Red +12V/24V Positive +12V DC Supply voltage for the reader.
0V/GND Black 0V 0V Supply Voltage for the reader.
RED Brown RED Red LED control output from the ACTpro 1520/1500. Connect the
reader brown cable to the terminal marked RED on the controller.
GREEN Yellow GREEN Green LED control output from the ACTpro 1520/1500. Connect the
reader green cable or terminal marked GREEN on the ACTpro
controller.
3.4 Wiring OSDP readers
When connecting OSDP readers to the ACTpro-1500 family of controllers, ensure that the EOL jumper is
on the last two pins (EOL position) on the last reader only.
Jumper position if controller is in the middle of the
OSDP-bus.
Jumper position if controller is EOL(End Of Line) for the
OSDP-bus.
You cannot network ACTpro-1500 controllers via RS485 when OSDP readers are attached. When
connecting controllers via RS485, move the jumper to the first two pins (standard operation).
Some examples of connecting OSDP readers:
Example 1
ACTpro-1500 Door Controller Installation and Operating Instructions Wiring
© Vanderbilt 2020 10 A-100667