Reader
Terminal
Block
Recommended
Wiring colour
Controller
Input PIN
Signal Information
0V/GND Black 0V 0V Supply Voltage for the reader.
RED Brown RED Red LED control output from the ACTpro controller or door stations.
Connect the reader brown cable to the terminal marked RED on the
controller.
GREEN Yellow GREEN Green LED control output from the ACTpro controller or door
stations. Connect the reader green cable or terminal marked
GREEN on the ACTpro controller.
3.3 Wiring Wiegand entry and exit readers
Label Description
A Entry reader. ACTpro-1050 PIN and Proximity reader (EM1050, MF1050, EV1050).
B Exit Reader. ACTpro-1030 Proximity reader (EM1030, MF1030, EV1030). Do not connect the reader to
the SENSE pin on the controller.
For Wiegand Entry Readers: Wire D0 to the DATA/D0 Pin on the ACTpro controller and D1 to the
CLOCK/D1 pin on the ACTpro controller.
For Wiegand Exit readers: Wire the D0 of the exit reader to the SENSE pin on the ACTpro controller
and D1 to the CLOCK/D1 pin on the ACTpro controller.
Max length: 100m with 12V DC
Cable: 8 core screened Belden 9504 (24 AWG) or equivalent
ACTpro-1500 Door Controller – Installation and Operating Instructions Wiring
© Vanderbilt 2020 9 A-100667