EasyManua.ls Logo

VAT 64246-UEHC-0001 - Page 23

VAT 64246-UEHC-0001
73 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Series 642
INSTALLATION
603685EA
Edition 2013-08-22
23/73
4.5.3.2 Sensor power wiring external
VAT fuse recommendation: (a) 5AF, (b) min. 3A
Use shielded sensor cable(s). Keep cable as short as possible, but locate it away
from noise sources.
Connect Power supply (+24 / GND) at power 5 pol. male connector and Sensors
(0V / + / -) at DB15 female sensor connector exactly as shown in the drawing
above!
Pins 2 and 3 must be
bridged for operation.
An optional switch
would allow for motor
interlock to prevent
valve from moving.
S C1 084 A