Liquid Sensor Alarms
MMM DD, YYYY HH:MM XM
L1 : FUEL ALARM
LIQUID STATUS
- - - - - - - - - - -
L 1: TANK 1
FUEL ALARM
MMM DD, YYYY HH:MM XM
consoles\qh\US\24.eps
MMM DD, YYYY HH:MM XM
L1 : SENSOR OUT ALARM
LIQUID STATUS
- - - - - - - - - - -
L 1: TANK 1
SENSOR OUT ALARM
MMM DD, YYYY HH:MM XM
consoles\qh\US\25.eps
14-09-97 19:25:47
T1 : INTERSTITIAL ALARM
INTERSTITIAL STATUS
- - - - - - - - - - -
L 1: TANK 1
LEAK ALARM
14-09-97 19:25
consoles\qh\26.eps
CAUSE:
The sensor shown has detected liquid in the
sump being monitored.
ACTION:
Silence the alarm by pressing the red ALARM/
TEST key.
Investigate the cause of the alarm and take
appropriate action.
CAUSE:
The sump sensor shown has been disconnect-
ed or is faulty.
ACTION:
Silence the alarm by pressing the red ALARM/
TEST key. Contact your VR Service Contractor
for advice.
CAUSE:
The Interstitial Monitor for the tank shown
has detected a change in the interstitial fluid
level; a fuel leak may have occurred.
ACTION:
Silence the alarm by pressing the red
ALARM/TEST key.
Call a Service Contractor to check for fluid
loss.

Other manuals for Veeder-Root TLS-350R PLUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS-350R PLUS and is the answer not in the manual?

Veeder-Root TLS-350R PLUS Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS-350R PLUS
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals