38
10 Diagnostics and servicing
VEGAPOINT 21 • Transistor (NPN/PNP)
56623-EN-210210
Function check: The instrument is being worked on, the measured
value is temporarily invalid (for example during simulation).
This status message is inactive by default.
Outofspecication: The measured value is unreliable because an
instrumentspecicationwasexceeded(e.g.electronicstemperature).
This status message is inactive by default.
Maintenance required:Duetoexternalinuences,theinstrument
functionislimited.Themeasurementisaected,butthemeasured
value is still valid. Plan in maintenance for the instrument because a
failure is expected in the near future (e.g. due to buildup).
This status message is inactive by default.
Code
Text message
Cause Rectication
F013
no measured value available
Error in capacitive measurement Send instrument for repair
F036
No operable software
Wrong software type
Software update not successful or
aborted
Repeat software update
F105
Measured value is deter-
mined
Device is still in the switch-on phase Wait for the end of the switch-on phase
F111
Switching points inter-
changed
Switching point 1 must be higher than
switching point 2
Repeat adjustment
F260
Error in the calibration
Error in the calibration carried out in the
factory
Error in the EEPROM
Send instrument for repair
F261
Error in the instrument set-
tings
Checksumerrorintheconguration
values
Carry out a reset
Code
Text message
Cause Rectication
C700
Simulation active
A simulation is active Finish simulation
Wait for the automatic end after
60 mins.
Code
Text message
Cause Rectication
S600
Impermissible electronics
temperature
Temperature of the electronics in the
non-speciedrange
Check ambient temperature
Insulate electronics
Failure
Function check
Outofspecication