Solar Pump Controller Manual
34
H-29
Sensor
disconnection alarm
operation selection
0:Continued operation
1:Close-down
0
31DH
H-30
Upper limit
demarcative values
Lower limit demarcative values
100.0%
100.0
31EH
H-31
lower limit
demarcative value
0.0%Upper limit demarcative
values
0.0
31FH
H-32
Lowest run
frequency
0.00Hz300.00Hz
20.00
320H
H-33
Lowest run
frequency duration
0.16500.0s 10.0
321H
H-34 Stop and wait time 0.16500.0s 30.0
322H
H-35
Automatic
dormancy voltage
01000V
323H
H-36
Renew voltage in
dormancy
01000V
324H
H-37
Max MPPT voltage
setting
01000V
325H
H-38
Min MPPT voltage
setting
01000V
326H
H-39
MPPT voltage
search interval
0.16500.0s 0.0
327H
H-40
MPPT voltage step
length
compensation
010.00Hz
1.00
328H
H-41 MPPT sample cycle
0.016500.00s 0.05
329H
H-42 Search repeat times
0100 2
32AH
H-43
DC current detect
measuring range
01000.0A
0.0A
32BH
H-44
Smallest power
change value can
be identified
01000.0w 2.0w
32CH
H-45
Pump power 0100.0KW
32DH
H-46
Search power
change value
01000W 10
32EH