Veichi SI10 - CVT Adjust Voltage Bias Limitation; Dry Run Protection Limit Current

Veichi SI10
42 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Solar Pump Controller Manual
35
H-47
Solar pump running
mode selection
LED 0 digit: Control mode
0: MPPT mode1
1:MPPT mode 2
2.MPPT mode 3
LED 10 digit: Search frequency step
0:Automatic calculate
1:User-defined
LED 100 digit: Dry run protection
0:Invalid
1: Valid
LED 1000 digit: CVT base voltage
adjust
0: Automatic setting
1: Manual
0000
●
32FH
H-48
Frequency step1 0~10.00HZ 0.80
●
330H
H-49
Frequency 1 0~600.00HZ
25.00
●
331H
H-50
Frequency step2 0~10.00HZ 0.30
●
32DH
H-51
Frequency 2 0~600.00HZ 32.00
●
32EH
H-52
Frequency step3 0~10.00HZ 0.15
●
32FH
H-53
Frequency 3 0~600.00HZ
40.00
●
330H
H-54
Frequency step4 0~10.00HZ 0.10
●
331H
H-55
Frequency 4 0~600.00HZ
45.00
●
332H
H-56
Frequency step 5 0~10.00HZ 0.80
●
338H
H-57
Frequency 5 0~600.00HZ 48.00
●
339H
H-58
Frequency step 6 0~10.00HZ 0.06
●
33AH
H-59
Quick reduce
frequency ratio
0~99.99%
96.0
0%
●
33BH
H-60
Long-term stop and
wait time
0~6000.0S
900.
0s
●
33CH
H-61
Repeat times in
dormancy
0~20 0
●
33DH
H-62 CVT base voltage
0~1000 ※
●
33BH
H-63 CVT adjust voltage
0~100%
80%
●
33BH
H-64
CVT adjust voltage
bias limitation
0~10.0%
0.0%
●
33BH
H-65
Dry run protection
limit current
0~1000.0A 0.0A
●
33EH
H-66
Linkage main
station setting
0:this machine is linkage slave station
1:main station mode 1
2: main station mode 2
0
●
342H
H-67 Machine addresses 1~247 1
●
343H