P-19
03/2006
Refrigeration:
1. Enter on Button 4 – ‘Set Point’
2.EnteronButton4–current‘SetPoint’willdisplay–(Factorysettingis36°F/2°C)
3.PressButton4–currenttemperaturewillash
4. Press Button 2 or 3 to scroll through the following settings:
Temperature setting 32 33 34 35 36 37 38 39 40
Cut-in Temperature (F) 34 35 36 37 38 39 40 41 42
Cut-out Temperature (F) 31 32 33 34 35 36 37 38 39
Nominal Temperature (F) 32 33 34 35 36 37 38 39 40
Nominal Temperature © 0 0.5 1 1.5 2 2.5 3 3.5 4
5. Press Button 4 to ‘save’ desired setting
7. Press Button 1 to exit – Set Point
8. Advance on Button 2 – Sensor Reading
9. Press Button 4 – Current reading in either F/C will display – must be set as Ref in
Congurationrst.
10. Press Button 1 – Sensor Reading
11. Advance on Button 2 – Degree F/C
12.EnteronButton4–currentsettingashes
13. Press Button 2 to scroll between F/C
14. Press Button 4 to save desired setting
Fan Default:
Default Mode: Fan on/off behaves in same respect as the compressor.
Mode 1: Fan is time delayed with compressor cut in/cut out
1. At cut in, fan will come on 1 minute after compressor turns on
2. At cut out, fan will continue to run 1 minute after compressor is off
3. Fan off with door switch activation