Deadband Settings (setup steps 17 - 20)
The Deadband is the number of degrees or
minutes that the thermostat waits before it
initiates the stages of heating or cooling.
1st Stage Deadband (Setup Step 17)
Speciesthetemperaturedifferencebetween
the room temperature and the desired setpoint
beforetherststageofheatingorcooling
isallowedtoturnon.(1-6degrees)For
example,iftheheatsetpointis68˚andthe1st
Stagedeadbandissetto2degrees,theroom
temperature will need to reach 66˚ before the
heat turns on.
2nd Stage Deadband (Setup Step 18)
Speciestheadditionaltemperaturedifference
aftertherststageturnsonbeforethesecond
stageisactivated.(0˚-10˚)
Minutes Between 1st and 2nd Stage
(Setup Step 19)
Speciestheminimumtime(inminutes)afterthe
rststageturnsonbeforethesecondstagecan
turnon.(0˚-60˚)
Second Stage Turnoff Point (Setup Step 20)
Specieswhethersecondstagewillturnoffat
rststagedeadbandorremainonuntiltheroom
temperaturedemandissatised.Choose
betweenDeadbandorSetpoint.