Deadband Settings (setup steps 17 - 20)
The Deadband is the number of degrees or
minutes that the thermostat waits before it
initiates the stages of heating or cooling.
1st Stage Deadband (Setup Step 17)
Speciesthetemperaturedifferencebetween
the room temperature and the desired setpoint
beforetherststageofheatingorcooling
isallowedtoturnon.(1-6degrees)For
example,iftheheatsetpointis68˚andthe1st
Stagedeadbandissetto2degrees,theroom
temperature will need to reach 66˚ before the
heat turns on.
2nd Stage Deadband (Setup Step 18)
Speciestheadditionaltemperaturedifference
aftertherststageturnsonbeforethesecond
stageisactivated.(0˚-10˚)
Minutes Between 1st and 2nd Stage
(Setup Step 19)
Speciestheminimumtime(inminutes)afterthe
rststageturnsonbeforethesecondstagecan
turnon.(0˚-60˚)
Second Stage Turnoff Point (Setup Step 20)
Specieswhethersecondstagewillturnoffat
rststagedeadbandorremainonuntiltheroom
temperaturedemandissatised.Choose
betweenDeadbandorSetpoint.