EXS
104 User Manual 10H52260UM60 - Rev. 1 - 10/2017
Menu Item Setting range Default setting
Battery test weekday
Sunday, Monday, Tuesday,
Wednesday, Thursday, Friday,
Saturday
Wednesday
Battery test time HH:MM:SS 0:00:00
Battery series 24, 32, 40 32
Discharge protect time
1
~
4320 (min)
4320
Equal charge enable YES, NO NO
Temperature compensation Enable, Disable Disable
Replace battery Button Button
Outlet
Turn on outlet
Appear only when outlet
off
Turn off outlet
Appear only when outlet
on
Reboot outlet
Appear only when outlet
on
Turn off when UPS overload on
battery
YES, NO NO
Turn off when UPS on battery
for
0
~
4320 (min)
2
Turn off when backup time less
than
0
~
4320 (min)
0
Turn off when battery capacity
less than
20
~
80%
30%
Turn on when power returns
for
0
~
4320 (min)
0
Monitor
Language English, Chinese English
Date YYYY-MM-DD 2016-10-01
Time HH:MM:SS 00:00:00
Display orientation Auto-rotate, Horizontal, Vertical Auto-rotate
Audible alarm Enable, Disable Enable
Control port protocol Modbus, Sensor Sensor
Modbus address
1
~
128
1
IPv4 address
ddd.ddd.ddd.ddd (where 'd' is a
decimal number)
192.168.1.10
Subnet mask 255.255.255.0
Gateway address 192.168.1.1
Change settings password
The password may be a numerical
value only and include any
character between 0 and 9. The
password length is 6 characters
111111