NOTE: High trips if the measurement goes above the threshold and low trips if the measurement goes
below the threshold.
b. Enter the desired Threshold Value (any number between -999.0 through 999.0).
c. Enter the desired Clear Delay time in seconds. Any value other than 0 means once this
event is tripped, the measurement must return to normal for this many seconds before
the event will clear and reset. Clear Delay can be up to 14400 seconds (4 hours).
d. Enter the desired Trip Delay time in seconds. Any value other than 0 means that the
measurement must exceed the threshold for this many seconds before the Event will be
tripped. Trip Delay can be up to 14400 seconds (4 hours).
e. Latching Mode: If enabled, this event and its associated actions remain active until the
event is acknowledged, even if the measurement subsequently returns to normal.
f. To specify where the alert notifications are sent when this alarm or warning event occurs,
click the Add icon to create a new action.
g. Select the desired options from the drop-down menu:
Target is the email address or SNMP manager to which notifications should be
sent when the event is tripped. For more information on configuring a target email
address see Email on page 43.
NOTE: Target Delays and Repeats are shared across all alarms. If multiple delay or repeat values are
needed for specific targets, each one must be added to the target list and then the appropriate Enabled
box checked on each alarm.
Delay determines how long this Event must remain tripped for before this
Action's first notification is sent. This is different from the Trip Delay above. Trip Delay
determines how long the threshold value has to be exceeded before the Event itself is
tripped. This delay determines how long the Event must remain tripped before this
Action occurs. Delay can be up to 14400 seconds (4 hours). A Delay of 0 will send the
notification immediately.
Repeat determines whether multiple notifications will be sent for this Event
Action. Repeat notifications are sent at the specified intervals until the Event is
acknowledged, or until the Event is cleared and re- set. The Repeat interval can be up to
14400 seconds (4 hours). A Repeat of 0 disables this feature, and only one notification will
be sent.
3. Click Save to save this notification action.
NOTE: More than one action can be set for an alarm or warning; to add multiple actions, just click the
Add icon again and set each one as desired. Each alert can have up to 32 Actions associated with it.
To change an existing alarm or warning event:
1. Click the Modify icon next to the alarm or warning event you wish to change.
2. Modify the settings as needed and click Save.
Vertiv | Intelligent Rack PDU Installer/User Guide
30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Geist GU2 Series and is the answer not in the manual?

Vertiv Geist GU2 Series Specifications

General IconGeneral
BrandVertiv
ModelGeist GU2 Series
CategoryPower distribution unit
LanguageEnglish

Related product manuals