Vertiv™ | Liebert® DM | Appendix Manual
120
Level 1 Level 2 Parameter Default Setting Range
Operation
and
maintenance
Optional function
Customer 3 polarity 0 0: NC 1: NO
Analog input 1
configuration
0
0: None; 1: Condensing pressure 1; 2:
Condensing pressure 2
Analog input 1 type 0 0: Voltage type; 1: Current type
ECO mode 0 0: Disabled; 1: Enabled
ECO mode start 22:00 0:00-23:00
ECO mode end 7:00 5:00-10:00
ECO mode proportional
band
2 0-10
Energy saving card type 1 0-1
Energy saving card
quantity
0 0-4
Sleep Temp.°C 27 ºC 15 ºC to 40 ºC
Energy saving card 1
Temp.°C
0 -40 ºC to 100 ºC
Energy saving card 2
Temp.°C
0 -40 ºC to 100 ºC
Energy saving card 3
Temp.°C
0 -40 ºC to 100 ºC
Energy saving card 4
Temp.°C
0 -40 ºC to 100 ºC