MODEL EDGE-500IRM1U EDGE-1000IRM1U EDGE-1500IRM1U
Power Rating @ 230V 500VA / 450W / 2.2A 1000VA / 900W / 4.4A 1500VA / 1350W / 6.7A
Output
Output Voltages (on battery) 200 / 208 / 220 / 230 / 240 VAC (230 VAC is factory default)
Output Frequency (on battery) Autodetect 50/60 Hz ±1%
Output Receptacles - not
controllable
(3) IEC 320 C13
Output Receptacles - controllable (3) IEC 320 C13
Transfer Time Adjustable with Input Waveform Sensitivity setting. SeeSettings Submenu for details.
Output Waveform (on Battery) Pure Sinewave
Output Overload Operation
101% - alarm warning
106% - alarm warning and shutdown after 60 seconds
126% - alarm warning and shutdown after 50 seconds
151% - alarm warning and shutdown after 2 seconds
201% - alarm warning and immediate shutdown
Protection Electronic (over current, short circuit w/ latching shutdown)
AC-mode Efficiency 98% or greater for 200/208/220/230/240 VAC
Buck- Boost1- and Boost2- mode
94% or greater for
200/208/220/230/240 VAC
96% or greater for 200/208/220/230/240 VAC
Recharge Time 4 hours to recover 90%
Internal Battery
Part Number EDGE-500I1UBATKIT EDGE-1000I1UBATKIT EDGE-1500I1UBATKIT
Protection Electronic (overcurrent, short circuit with latching shutdown)
Type Valve-regulated lead-acid (VRLA) in compliance with UL 1989
Quantity x Voltage x Ah 2 x 6V x 9Ah 4 x 6V x 9Ah 6 x 6V x 9Ah
Environment
Operating temperature 0 °C to 40 °C
Storage temperature - 25 °C to +55 °C without battery inside
Relative Humidity (Operation) 20% to 90%, non-condensing
Operating Altitude 3000 m @ 0°C to 40 °C without derating
Audible Noise
<45 dBA AVR mode, >70% load
<55 dBA Battery mode
Agency
Table 6.1 Specifications, EDGE-500IRM1U,EDGE-1000IRM1U and EDGE-1500IRM1U (continued)