MODEL EDGE-750IMT EDGE-1000IMT EDGE-1500IMT
Power Rating @ 230V 750VA / 675W / 3.3A 1000VA / 900W / 4.4A 1500VA / 1350W / 6.7A
Frequency Input Range
45 to 65 Hz
Autodetect 50 / 60 Hz
Battery to Normalcomeback at 50Hz: 47 to 53Hz
Battery to Normalcomeback at 60Hz: 57 to 63Hz
Internal Rear-panel Input Breaker
Rating
5 A 8 A 10 A
Input Surge Protection EN61000-4-5; Line to Line: Level 2; Line to Earth: Level 3 (624J L/N, 624J L/G, 624J N/G)
Input Power Receptacle IEC 320 C14
Output
Output Voltages (on battery) 200 / 208 / 220 / 230 / 240 VAC (230 VAC is factory default)
Output Frequency (on battery) Autodetect 50/60 Hz ±1%
Output Receptacles - not
controllable
(3) IEC 320 C13
Output Receptacles - controllable (2) IEC 320 C13 (3) IEC 320 C13
Transfer Time Adjustable with Input Waveform Sensitivity setting. See Settings Submenu for details.
Output Waveform (on Battery) Pure Sinewave
Output Overload Operation
101% - alarm warning
106% - alarm warning and shutdown after 60 seconds
126% - alarm warning and shutdown after 50 seconds
151% - alarm warning and shutdown after 2 seconds
201% - alarm warning and immediate shutdown
Protection Electronic (over current, short circuit w/ latching shutdown)
AC-mode Efficiency 98% or greater for 200/208/220/230/240 VAC
Buck- Boost1- and Boost2- mode
95% or greater for
200/208/220/230/240 VAC
96% or greater for 200/208/220/230/240 VAC
Recharge Time 4 hours to recover 90%
Internal Battery
Part Number EDGE-750IMTBATKIT EDGE-1000IMTBATKIT EDGE-1500IMTBATKIT
Protection Electronic (overcurrent, short circuit with latching shutdown)
Type Valve-regulated lead-acid (VRLA) in compliance with UL 1989
Quantity x Voltage x Ah 2 x 12V x 9Ah 2 x 12V x 10Ah 4 x 12V x 9Ah
Environment
Operating temperature 0 °C to 40 °C
Storage temperature - 25 °C to +55 °C without battery inside
Relative Humidity (Operation) 20% to 90%, non-condensing
Table 6.2 Specifications, EDGE-750IMT, EDGE-1000IMT and EDGE-1500IMT (continued)
6 Specifications
46
Liebert® EDGE Installer/User Guide