MODEL EDGE-1500IRT2UXL EDGE-2200IRT2UXL EDGE-3000IRT2UXL EDGE-3000IRT3UXL
Power Rating @ 230V 1500VA / 1350W / 6.7 A 2200VA / 1980W / 9.8A 3000VA / 2700W / 13.3A
Output Overload
Operation
101% - alarm warning
106% - alarm warning and shutdown after 60 seconds
126% - alarm warning and shutdown after 50 seconds
151% - alarm warning and shutdown after 2 seconds
201% - alarm warning and immediate shutdown
Protection Electronic (over current, short circuit w/ latching shutdown)
AC-mode Efficiency 98% or greater for 200/208/220/230/240 VAC
Buck- Boost1- and
Boost2- mode
96% or greater for 200/208/220/230/240 VAC
Recharge Time 4 hours to recover 90%
Internal Battery
Part Number
EDGE-
1500IRT2UBATKIT
EDGE-
2200IRT2UBATKIT
EDGE-
3000IRT2UBATKIT
EDGE-
3000IRT3UBATKIT
Protection Electronic (overcurrent, short circuit with latching shutdown)
Type Valve-regulated lead-acid (VRLA) in compliance with UL 1989
Quantity x Voltage x Ah 4 x 12V x 9Ah 6 x 12V x 7Ah 6 x 12V x 10Ah
External Battery Cabinets
Model Number GXT5-EBC48VRT2U GXT5-EBC72VRT2U
Type Valve-regulated lead-acid (VRLA) in compliance with UL 1989
Protection Circuit breaker
Quantity x Voltage x Ah 4 x 12V x 9Ah 6 x 12V x 9Ah
Dimensions, W x D x H,
mm
430 x 497 × 85 430 x 602 x 85
Shipping dimensions, W
x D x H, mm
570 x 617 x 262
Unit weights, kg 28.5 39
Dimensions, W x D x H,
mm
41.5 50
Environment
Operating temperature 0 °C to 40 °C
Storage temperature - 25 °C to +55 °C without battery inside
Relative Humidity
(Operation)
20% to 90%, non-condensing
Operating Altitude 3000 m @ 0°C to 40 °C without derating
Table 6.3 Specifications, EDGE-1500IRT2UXL, EDGE-2200IRT2UXL,EDGE-3000IRT2UXL and EDGE-
3000IRT3UXL (continued)
6 Specifications
49