Specications66
Table 7-2 UPS Specications, 8-kVA and 10-kVA models (Continued)
MODEL: GXT5 8000IRT5UXLN 8000IRT5UXLE 8000HVRT5UXLN 10KIRT5UXLN 10KIRT5UXLE 10KHVRT5UXLN
RATING 8000 VA/8000 W 10000 VA/10000 W
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x Voltage
x Rating
16 x 12V x 9.0AH
Battery Mfr./Part # 9AH; LEOCH/DJW12-9.0
Back-up time See Table 7.9 on page 70. See Table 7.8 on page 70.
Upper-limit
selections
+10%, +15%, +20%; default +10%.
Lower-limit
selections
-10%, -15%, -20%; default -15%
Disable-bypass
operation
When the input frequency prevents synchronous operation.
Environmental Parameters
Operating
Temperature, °C
(°F)
0 to 40 (32 to 104) (no derating)
Storage
Temperature, °C
(°F)
-15 to 40 (5 to 104)
Relative Humidity 0 – 95% non-condensing
Operating Elevation Up to 3,000 m (9,842.5 ft) at 2C (77°F) without derating
Audible Noise <55 dBA, at 1 meter from the front, <50 dBA, at 1 meter from rear or sides
Agency Parameters
Safety IEC62040-1:2008 version, GS mark
IEC62040-1:2008
version, GS mark;
UL1778, c-UL listed
IEC62040-1:2008 version, GS mark
IEC62040-
1:2008 version, GS
mark; UL1778, c-UL
listed
EMI/EMC/C-Tick
EMC
IEC/EN/AS 62040-2 2nd Ed (Cat 2
– Table 6)
IEC/EN/AS 62040-
2 2nd Ed (Cat 2 –
Table 6);
FCC Part 15 (Class A)
CISPR22 Class A
(RFI)
IEC/EN/AS 62040-2 2nd Ed
(Cat 2 – Table 6)
IEC/EN/AS 62040-
2 2nd Ed
(Cat 2 – Table 6);
FCC Part 15 (Class
A) CISPR22 Class
A (RFI)
ESD
IEC/EN EN61000-4-2, Level 4,
Criteria A
IEC/EN EN61000-
4-2, Level 4, Criteria
A
IEC/EN EN61000-4-2, Level 4,
Criteria A
IEC/EN EN61000-
4-2,
Level 4, Criteria A
Radiated
Susceptibility
IEC/EN EN61000-4-3, Level 3,
Criteria A
IEC/EN EN61000-
4-3, Level 3, Criteria
A
IEC/EN EN61000-4-3, Level 3,
Criteria A
IEC/EN EN61000-
4-3,
Level 3, Criteria A
Electrical Fast
Transient
IEC/EN EN61000-4-4, Level 4,
Criteria A
IEC/EN EN61000-
4-4, Level 4, Criteria
A
IEC/EN EN61000-4-4, Level 4,
Criteria A
IEC/EN EN61000-
4-4,
Level 4, Criteria A
Surge Immunity
IEC/EN EN61000-4-5, Level 4,
Criteria A
IEC/EN EN61000-
4-5, Level 4, Criteria
A;
ANSI C62.41
Category B
IEC/EN EN61000-4-5, Level 4,
Criteria A
IEC/EN EN61000-
4-5,
Level 4, Criteria A;
ANSI C62.41
Category B
Transportation ISTA Procedure 1E

Other manuals for Vertiv LIEBERT GXT5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv LIEBERT GXT5 Series and is the answer not in the manual?

Vertiv LIEBERT GXT5 Series Specifications

General IconGeneral
ModelLIEBERT GXT5 Series
Product TypeUPS
TopologyDouble Conversion Online
DisplayLCD
Form FactorTower, Rackmount
Output Voltage200/208/220/230/240 VAC
Output Frequency50/60Hz ±0.1Hz (battery mode)
Typical Backup TimeVaries by model and load
Communication PortsUSB, RS-232
Operating Temperature0°C to 40°C (32°F to 104°F)
Relative Humidity0% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model
CertificationsUL, cUL, CE, RoHS
Battery TypeValve Regulated Lead Acid (VRLA)