4. The following window opens.
Figure 88. Upload/Download File
ALERT! Never navigate from this Web page without first clicking on "Start Controller". If you do, you will not have Web access.
A manual system reset is required to restore Web access.
5. To download (from your computer into the controller) a configuration package, application ("All") package, language package,
or a "SettingParam.run" file; click the "Browse..." button and navigate to the folder where the file to download is located. Select
the file to be downloaded and then click the "Download to Controller" button. Click "Start Controller" to restart the controller
with the downloaded file installed.
To upload a file to your computer, select "Configuration Package" or "Language Package" from the "File in Controller" drop-down
list box, and click on the "Upload to Computer" button to save the file to your computer. Select where you want the file to be
copied to on your computer. Click "Start Controller" to restart the Controller.
NOTE: Ensure Internet Explorer security settings are set to enable a file to be copied to your computer.
NOTE: A Configuration Package is a package of files containing all the default parameter settings and any User changes to alarm severity
levels, relay assignments, signal names and site information.
NOTE: An Application “All” package file has both the application (software) and configuration package and is usually supplied for an
application upgrade.
NOTE: A Language Package is a package of files containing all the default names of the parameters in two languages. Typically these
would be in English and Chinese. The language package cannot be changed by the User. Consult Vertiv if a different language package is
required.
NOTE: A file named “SettingParam.run” is automatically created/appended by the Controller whenever a User (or the factory at the time