5.2 Mechanical installation
The Vetaphone iPM200 generator module uses forced air-cooling and thereby have to be mounted
vertically on the wall, inside the customer enclosure with 4 x M6 screws. Use the mounting holes in the
top and bottom of the generator module, see figure 5.2
The enclosure that the generator module is installed in MUST at least be IP20.
Generator must be mounted inside an enclosure and the enclosure must meet the minimum distance
requirements of table 5.2.1 for instalment without extern ventilator or the requirements of table 5.2.2 for
instalment without with ventilator
Figure 5.2: Mounting of the iPM200 module.