Vitocal 300, type BW 110 and WW 110 (single stage)
A Heating output
B Refrigerating capacity
C Power consumpti on
D T
HV
=35°C
E T
HV
=45°C
F T
HV
=55°C
PerformancedatatypeBW110
Operating point B0/W35 B2/W45 B2/W55
Heating output kW 10.80 11.10 10.60
Refrigerating capa-
city
kW 8.40 8.10 7.00
Power consumption kW 2.40 3.00 3.60
Coefficient of Performance
∊ (COP)
4.50 3.70 2.94
PerformancedatatypeWW110
Operating point W10/W35 W8/W45 W8/W55
Heating output kW 14.20 12.90 12.40
Refrigerating capa-
city
kW 11.70 9.80 8.68
Power consumption kW 2.50 3.10 3.75
Coefficient of Performance
∊ (COP)
5.68 4.16 3.31
5822 119-7 GB
14 VIESMANN VITOCAL 300/350
Output diagrams for the Vitocal 300 (single stage) (cont.)