Vitocal 350, type BWH 110 and WWH 110
A Heating output
B Refrigerating capacity
C Power consumpti on
D T
HV
=35°C
E T
HV
=45°C
F T
HV
=55°C
G T
HV
=65°C
Note
COP details i n the following tables and diagrams calculated with
reference to DIN EN 255.
PerformancedatatypeBWH110
Operating point B0/W35 B2/W55 B2/W65
Heating output kW 11.00 13.20 13.20
Refrigerating capa-
city
kW 8.45 9.00 8.10
Power consumption kW 2.55 4.20 5.10
Coefficient of Performance
∊ (COP)
4.31 3.14 2.59
PerformancedatatypeWWH110
Operating point W10/W35 W8/W55 W8/W65
Heating output kW 14.10 14.60 14.90
Refrigerating capa-
city
kW 11.40 10.30 9.45
Power consumption kW 2.70 4.30 5.15
Coefficient of Performance
∊ (COP)
5.22 3.39 2.83
5822 119-7 GB
22 VIESMANN VITOCAL 300/350
Output diagrams for the Vitocal 350