Vitocal 300, type BW 212 and WW 212 (two-stage)
A Heating output
B Refrigerating capacity
C Power consumpti on
D T
HV
=35°C
E T
HV
=45°C
F T
HV
=55°C
Note
COP details i n the following tables and diagrams calculated with
reference to DIN EN 255.
Performance data type BW 212
Operating point B0/W35 B2/W45 B2/W55
Heating output kW 12.80 13.20 12.40
Refrigerating capa-
city
kW 10.00 9.60 8.20
Power consumption kW 2.80 3.50 4.20
Coefficient of Performance
∊ (COP)
4.56 3.75 2.94
Performance data type WW 212
Operating point W10/W35 W8/W45 W8/W55
Heating output kW 16.80 15.20 14.20
Refrigerating capa-
city
kW 13.80 11.50 10.10
Power consumption kW 3.00 3.70 4.50
Coefficient of Performance
∊ (COP)
5.58 4.09 3.22
5822 119-7 GB
VITOCAL 300/350 VIESMANN 17
Output diagrams for the Vitocal 300 (two-stage)